Helpful video reference. This installation guide from Electric Radiators Direct, a UK electric heating retailer, covers the installation considerations for an outdoor electric heater, including mounting options and supply requirements. Worth watching to understand the practical steps before starting your own installation.
1. Check the heater's electrical specification and IP rating
Read the manufacturer's data sheet before buying any accessories or cable. Note the rated power in watts or kilowatts, the supply type (plug-in or hardwired), and the IP rating of the heater body itself.
Most domestic patio heaters are between 1.5 kW and 3 kW, drawing up to 13 A at 230 V. This puts them within the capacity of a 13 A socket supplied from the ring final. Larger commercial-grade units may need a dedicated circuit. Check the data sheet -- the manufacturer will specify.
The heater's IP rating tells you how weatherproof the unit itself is, but it does not govern what the accessories and cable supply need to be. Those are determined by their mounting position in the open air.
2. Plan the cable route and protection method
There are three common routes for an outdoor patio heater supply:
Surface-run on the house wall: Cable clipped to the wall in UV-resistant conduit or trunking, running from an indoor socket or consumer unit to an outdoor accessory. This is the most straightforward route. The conduit protects the cable from mechanical damage and UV degradation.
Through the wall: Short section from an indoor accessory through the cavity or solid wall to an outdoor back box. The hole must be sleeved and sealed against damp penetration -- drill at a slight downward angle toward the outside so water cannot track in.
Underground: Where the cable must cross a patio or lawn, it must either be armoured cable (SWA) buried at a minimum depth of 500 mm, or an unarmoured cable drawn through rigid conduit buried at the same depth. Mark the route and record it so the cable is not damaged later by digging.
3. Fit a 30 mA RCD-protected circuit or fused spur
BS 7671 regulation 411.3.3 requires 30 mA RCD protection for all outdoor socket outlets. Amendment 2 to the 18th Edition (2022) extended this requirement to all domestic circuits, so a hardwired outdoor supply also requires 30 mA RCD protection.
If the heater is plug-in and the outdoor socket will be fed from the ring final, the simplest solution is a fused spur with a 13 A fuse, supplied from an existing ring circuit protected by a 30 mA RCD at the consumer unit. If your consumer unit has a main RCD covering all circuits, the outdoor spur is already protected. If not, fit a local 30 mA RCD socket or FCU with built-in RCD.
If the heater is hardwired and draws more than 13 A, fit a dedicated RCBO at the consumer unit sized to the heater's rated current.
4. Install IP65-rated outdoor accessories
Every accessory mounted outdoors -- the socket, FCU, or switched spur -- must be rated for outdoor use. For fully exposed positions, IP65 is the appropriate rating. For positions under a deep overhang where the accessory will never be wetted directly, IP44 may be sufficient, but IP65 is the better choice for all outdoor use.
Use a weatherproof surface back box (the kind with a sealing gasket around the faceplate) rather than a standard dry-lining box. Cable entry points on outdoor back boxes must be sealed -- use the gland fittings supplied with the surface box, or IP-rated cable glands if the entry is from conduit.
Tighten all cover screws evenly so the gasket seats fully. A partially tightened outdoor socket loses its IP rating and will allow moisture in.
5. Run and terminate the cable
For a surface run in conduit on the building fabric: use 2.5 mm2 twin-and-earth in UV-stabilised round conduit. Clip the conduit at 500 mm intervals. At the building penetration point, seal around the conduit with an appropriate mastic or expanding foam.
For an underground run in SWA: strip the outer sheath carefully with an armoured cable stripper, not a knife, to avoid nicking the wire armour. Terminate the armour in an SWA cable gland that provides both mechanical grip and an earth connection via the gland body. The armour must be earthed at both ends.
At the accessory, strip only the length of insulation that fits the terminal -- typically 10 mm. Do not leave bare conductor visible beyond the terminal. Tighten screw terminals firmly; finger-tight is not sufficient for outdoor accessories that may experience thermal cycling.
6. Make the final connection to the heater
If the heater is plug-in: install the outdoor socket, restore power, and use an RCD tester to confirm the protective device trips at 30 mA before plugging in the heater. Then plug in and test.
If the heater is hardwired: the final connection point is usually inside the heater's wiring compartment, accessed via a removable cover. Follow the manufacturer's wiring diagram. Connect brown to L, blue to N, and green-and-yellow to the earth terminal. Replace the cover and all weather seals. The heater should have a local isolator -- a switched FCU or a double-pole isolator on the wall -- so it can be de-energised without going to the consumer unit.
7. Test and record the installation
Carry out the required inspections and tests under BS 7671 Chapter 61 before leaving the job: insulation resistance, polarity, earth continuity, and RCD operating time. For a new circuit, issue a Minor Electrical Installation Works Certificate (if adding a spur to an existing circuit) or an Electrical Installation Certificate (if adding a new circuit from the consumer unit).
If you are a homeowner carrying out your own work: notify Building Control before you start, not after. Their inspector will want to see the installation before it is concealed (underground sections especially) and again on completion.
When to call us
Richard supplies and certifies outdoor circuits for patio heaters, garden offices, outbuildings, and EV chargers across Sandwich and east Kent. If the job involves a new consumer unit way or underground cable, he can price the full scope at once.