Installing a NexBlue Edge EV charger: what the job involves

The NexBlue Edge is a wall-mounted EV charger that covers both single-phase (7.4 kW) and three-phase (22 kW) supplies, making it one of the more versatile options for homes that might eventually upgrade from single to three-phase. Installing one in a UK home is notifiable work under Part P of the Building Regulations and must be done by a qualified electrician. One thing to plan for: the Edge (UK) needs an external 30 mA Type A RCD, which is not included inside the unit as it is in many rival chargers.

Video reference. The team at eFIXX, a UK electrical trade media channel run by and for electricians, review the NexBlue charger in "eFIXX Reviews the NexBlue Charger". The review covers unboxing, installation observations and practical assessment from a UK electrician's perspective.

This is not a DIY job. A NexBlue Edge installation involves a new circuit from the consumer unit, which is notifiable work under Part P of the Building Regulations. It must be carried out by a qualified electrician. The steps below explain what a professional installer will do, so you understand the job before getting quotes.

1. Identifying your phase supply and choosing the right Edge variant

The NexBlue Edge (UK) is designed to work on both single-phase and three-phase supplies. The vast majority of UK homes are single-phase, which gives you 7.4 kW (32A) charging. Three-phase at 22 kW is only available where you have a three-phase service, which is relatively uncommon in domestic properties and usually found only in larger detached houses or commercial buildings.

Your electrician can confirm your phase supply by checking the cut-out in your meter cupboard. If you are single-phase now but considering a future upgrade, the Edge is designed to handle both without swapping the unit. For most UK homes, the single-phase 7.4 kW option is what matters day to day.

NexBlue also sells the Edge 2 and Edge Max, which are newer models with OCPP 2.0.1, ISO 15118 Plug and Charge and a five-year warranty. The standard Edge (UK) uses OCPP 1.6J and is the more widely available option.

2. Assessing the consumer unit and choosing the mounting position

Your electrician will confirm the consumer unit has a spare way for a new 32A RCBO and check that the incoming supply can carry the additional load. For a 7.4 kW (32A) circuit on a standard 100A single-phase supply this is usually straightforward, but the electrician will measure live load during peak use to be sure.

The Edge is IP54 rated so it can mount outdoors. Choose a spot close to where you park, at around 0.8 m to 1.2 m from the ground. For a garage installation, the cable route into the consumer unit determines how practical each wall position actually is.

3. Running the supply cable

A single-phase 7.4 kW installation uses 6 mm two-core and earth cable on a 32A circuit. For a three-phase 22 kW installation the cable is heavier gauge and three-phase: your electrician will specify the correct cable size based on the route length. For either, a driveway crossing requires armoured SWA cable buried at least 450 mm deep.

4. Fitting the RCBO and external Type A RCD

This is the step that catches some people out. Unlike many home EV chargers that include RCD protection inside the unit, the NexBlue Edge (UK) requires a separate external 30 mA Type A RCD. Your electrician will fit this between the consumer unit and the charger, either in its own enclosure or in-line with the supply cable close to the charger. A 32A RCBO in the consumer unit provides overcurrent protection.

The Type A RCD protects against pulsating DC leakage currents, which are present during Mode 3 AC EV charging. BS 7671 requires this level of protection on EV charging circuits. It is not optional.

5. Mounting the backplate and wiring the unit

The Edge uses a separate backplate that goes on the wall first. This lets all cable work be completed and checked before the front unit is fitted. Your electrician will thread the supply cable through the entry gland, connect Line, Neutral and Earth to the correct terminals, and tighten the gland to maintain the IP54 weatherproof rating. For a tethered version, the cable is pre-fitted at the factory.

6. Commissioning and configuring

Once power is restored, the Edge is commissioned through the MyNexBlue app. Your electrician will check the display initialises correctly and that the unit pairs with the app. You can then set up:

This job must be done by a qualified electrician. Part P notification is required for all new circuits. If you qualify for the OZEV Electric Vehicle Chargepoint Grant, the work must be done by an OZEV-registered installer. Always request an Electrical Installation Certificate on completion.