How to use a cable avoidance tool (CAT and genny) safely

Striking a buried cable is one of the most preventable serious accidents in electrical work. A CAT and genny do not find everything, but they find far more than guesswork does. This guide covers how to use one correctly on a domestic job in the UK.

Helpful video reference. We use Paragon Training's UK health and safety video "CAT & Genny - Safe Use of Cable Avoidance Tools Safety Training Video UK" as the video reference here. Paragon Training is a UK health and safety training company and this video covers the correct procedure in a UK context, including the Health and Safety at Work Act obligations for anyone carrying out ground-breaking or drilling work near buried services.

Before you start. A CAT and genny do not detect every buried service. Non-metallic pipes (MDPE gas, blue water main) give no signal. Records from utility companies and Dial Before You Dig remain essential. Never assume a clear CAT reading means nothing is buried.

1. Obtain utility records before you do anything else

Contact the relevant utility companies using a records service. In the UK, you can request drawings from National Grid, the local DNO, Cadent Gas, and your water company. The Linesearch Before U Dig (LSBUD) service consolidates many of these requests. Allow enough lead time - in a domestic setting this is often overlooked, but records frequently reveal cables in positions you would not expect.

Cross-reference any records with the site: look for surface features such as lamp-post feeds, meter boxes, gate motors, and pond pumps that indicate buried cables nearby.

2. Understand the three detection modes

A cable avoidance tool has three detection modes. You must use all three - each finds services the others can miss.

Sweep the whole area in power and radio modes first, before you place the genny. This avoids the risk of the genny signal masking another buried service.

3. Apply the genny signal

The signal generator (genny) induces a distinctive radio frequency signal onto a metallic service so the CAT can trace it precisely. There are two ways to apply it.

Once the genny is in place, set the CAT to genny mode. Walk slowly along the expected cable route to confirm the route, then proceed to a full area sweep.

4. Sweep in genny mode

Hold the CAT wand vertical and move it slowly across the ground, perpendicular to the expected cable run. The signal peaks directly over a buried service and drops off sharply to either side. This peak-response method gives you the most accurate location.

Do not hold the wand at an angle: a tilted wand shifts the peak response off-centre and gives a false position. Keep it vertical and move it at a steady walking pace.

For depth indication, rotate the CAT by 90 degrees so the wand points forward. Many modern units display an estimated depth reading in this orientation. Treat depth estimates as approximate - ground conditions affect accuracy.

5. Sweep in a grid pattern

A single sweep only finds cables running roughly parallel to your direction of travel. Services can run in any direction, so you must sweep the whole area in a grid.

This cross-pattern means cables at any orientation will be crossed by at least one sweep and produce a clear peak response.

6. Mark up every detection

Mark each detected service the moment you find it. Use contractor marking spray (the colour convention in the UK follows PAS 128: red for power, yellow for gas, blue for water, green for telecoms) or stakes with tape. Take a photograph of the marked area showing all detections before you start any digging or drilling.

Record the sweep in your method statement or permit to work log if one is in use. On a domestic job this is often informal, but a marked-up photograph on your phone is far better than nothing.

Stop and call an electrician if: the CAT detects an unexpected signal near where you planned to dig, the records show a service but you cannot trace it with the genny, or you find any cable that appears damaged, exposed, or in an unusual position. Do not dig through an unidentified signal.