5% off for pensioners

How-to · UK domestic

How to test earth electrode resistance with an MFT

TT installations (mostly properties with overhead supplies, older rural homes, and outbuildings with a separate earth electrode) rely on the earth rod for their fault protection. The resistance of that rod, Ra, must be low enough to ensure the RCD operates within its rated trip current. This guide explains how to measure it using the fall-of-potential method on a multifunction tester.

Helpful video reference. Megger's "How to do Earth Electrode RESISTANCE Test! Megger MFT X1 Tutorial" demonstrates the full fall-of-potential procedure using a Megger MFT. Megger is a UK test equipment manufacturer whose instruments are standard issue on UK installations. The video is technically accurate and specific to UK practice.

Before you start. The installation must be isolated at the consumer unit before disconnecting the earth electrode. Working on an energised installation with the earthing disconnected is extremely dangerous: the whole installation becomes unearthed. Confirm the supply is isolated and test dead before touching the earthing conductor. Only reconnect the electrode once the test is complete and the earthing conductor has been re-secured.

1. Understand what you are measuring

Earth electrode resistance (Ra) is the resistance between the surface of the earth rod and remote earth (the general mass of earth far enough away to be unaffected by the current injected during the test). It is not the same as the earth fault loop impedance you measure with the MFT in Zs mode during a standard test sequence.

The relevant regulation is BS 7671 Regulation 411.5.3, which states:

Ra × I∆n ≤ 50 V

Where Ra is the electrode resistance in ohms and I∆n is the rated residual current of the RCD in amps. For a standard 30mA (0.03A) RCD protecting a socket circuit, this means Ra must be 50 ÷ 0.03 = 1,667Ω or less. That sounds generous, but a reading of 1,500Ω gives almost no margin. Most electricians and inspection guides use 200Ω as a practical target, with values below 100Ω considered good.

In sandy or chalky soils like much of east Kent, electrode resistance can be higher than in clay-heavy ground, particularly in dry summers. This is worth factoring into the test timing.

2. Gather your equipment

You need:

3. Temporarily disconnect the electrode from the installation

Isolate the installation at the consumer unit and test dead. Then disconnect the earthing conductor from the earth electrode terminal. Many earth electrodes have a clamp or bolted connection at the top of the rod where it enters the ground or an inspection pit - this is where the conductor disconnects.

Keep the disconnected earthing conductor safe and out of the way. The installation has no earth path now. Do not restore power until the conductor is reconnected after the test.

4. Drive the auxiliary current and potential spikes

The standard UK method for positioning auxiliary spikes follows the 62% rule from BS 7430:

  1. Measure or estimate the depth of the earth electrode (D). For a standard 1.2m copper-clad steel rod, D = 1.2m.
  2. Drive the current spike (C2) in a straight line away from the electrode at a distance of at least 10 × D. For a 1.2m rod, that is at least 12m away. In practice, 25m to 30m gives better results in typical UK soil conditions.
  3. Drive the potential spike (P2) in a straight line between the electrode and C2, at 62% of the distance to C2. So if C2 is 25m away, P2 goes at 25 × 0.62 = 15.5m from the electrode.

All three points (the electrode, P2 and C2) should be in a straight line. If site constraints force a triangle arrangement, the error increases - note this in your records.

5. Set up the MFT and run the measurement

Connect the test leads to the MFT terminals:

Select the earth electrode resistance function on the MFT. Press the test button and hold. The MFT injects a small AC test current (typically around 25mA at a frequency not synchronised with mains, to avoid interference) between the electrode and C2, and measures the resulting voltage between the electrode and P2. It divides voltage by current to calculate resistance and displays the result in ohms.

Read the result and note it down.

6. Verify with spike transpositions (the 62% check)

A single reading can be affected by underground metalwork, services or resistivity variations in the soil. The 62% check confirms the result is valid:

  1. Move P2 5% of the electrode-to-C2 distance closer to the electrode. Re-test and note the reading.
  2. Move P2 5% further from the original 62% position (now 67% of the electrode-to-C2 distance). Re-test and note the reading.

If all three readings are within approximately 10% of each other, the 62% method has given a valid result and the middle reading (at the 62% position) is your Ra value. If they vary more than that, the spikes need to be spaced further apart - the resistance zones of the electrode and C2 are overlapping. Increase the electrode-to-C2 distance and repeat.

7. Reconnect and record the result

Reconnect the earthing conductor to the earth electrode and tighten the clamp securely. Restore power at the consumer unit.

Record the following in your test results:

If Ra exceeds the calculated limit for the installed RCD, the electrode is inadequate. Options are: driving the rod deeper, driving an additional electrode and connecting them in parallel, or treating the soil with bentonite clay to lower resistivity. If in doubt, call an electrician to advise.

Stop and call an electrician if: the measured Ra value when multiplied by the RCD trip current exceeds 50V; you cannot get consistent readings with the transposition check; you discover the installation has no earth electrode and has been relying on a PME supply earth (common in outbuildings where a TT electrode is required but was never installed); or you are not confident about any step of the isolation procedure.

When to call us

Earth electrode testing is part of every EICR on a TT installation and every initial verification on a new outbuilding supply. Richard tests and certifies earthing arrangements across Sandwich and east Kent, and can advise on improving a poor result.

Need an EICR or earthing check in east Kent?

Richard carries out EICRs, initial verifications and earth electrode testing across Sandwich, Deal, Dover, Ramsgate and Canterbury. Results and certificates issued on the same day in most cases.

Contact Richard

Related pages