How-to · UK domestic

How to wire a bathroom extractor fan

A bathroom extractor fan is one of the most effective ways to prevent damp and condensation, but the wiring has a few UK-specific twists: bathroom zones under BS 7671, the over-run timer setting, and the rule that wall switches cannot be within reach of the bath or shower. Get those right and the job is manageable for a careful DIYer.

Helpful video reference. John Ward (jwflame), a UK electrician based in Dorset, explains bathroom extractor fan wiring in his video "How to wire bathroom fan UK". John covers the switching options clearly — including how to connect the fan so it runs and over-runs via the light switch — and stays UK-specific throughout, including the correct colours for current harmonised cable. Worth watching alongside the installation instructions for your particular fan, as terminal labelling varies between manufacturers.

Before you start. Turn the lighting circuit off at the consumer unit, not just at the wall switch. Confirm dead at the ceiling rose or junction box you intend to tap with an approved voltage tester. Bathroom electrics carry their own regulations under BS 7671, and if you are unsure which zone the fan position falls in, measure before you commit — fitting a non-IP-rated fan in the wrong zone is a C2 fault on any subsequent EICR.

1. Identify the bathroom zone

BS 7671 defines three zones in a bathroom:

Measure from the shower tray or bath edge to the fan position. Note it down. If the fan sits in zone 1 or 2, make sure the model you have chosen carries the correct zone rating on its specification sheet.

2. Isolate the supply

Switch off the lighting circuit at the consumer unit. Test at the existing ceiling rose with a voltage tester. If the bathroom light is on a separate circuit from the rest of the floor, both circuits may need isolating before you work safely in the ceiling void.

3. Choose your switching method

There are four common arrangements in UK bathrooms:

For most bathrooms, the light-switch method is the right choice. The guide from here assumes that arrangement.

4. Fit the fan housing

Mark the fan position on the ceiling. Use a hole saw of the correct diameter — typically 100 mm for a standard domestic fan, but always check the fan's installation sheet. Drill a pilot hole first and probe above with a bent wire to check for obstructions. Fit the fan body to the ceiling using the joist above or appropriate hollow-wall fixings. Do not let the fan hang unsupported from the wiring.

5. Run the ducting

Connect rigid or semi-rigid ducting from the fan outlet to an external wall vent, soffit tile or roof vent. The duct must have a continuous fall towards the outside so condensation drains away. Keep bends as gentle and as few as possible — a long tortuous duct kills airflow and the fan becomes useless. Avoid flexible concertina duct if you can: it traps water in the corrugations.

Fit a back-draught shutter or non-return valve at the external vent to prevent cold air entering when the fan is off.

6. Run the supply cable

The fan needs a permanent live and a switched live taken from the lighting circuit. The easiest source is the ceiling rose or a new junction box on the loop-in lighting cable. Use 1.0 mm three-core and earth (brown, grey or black switched live, and blue neutral) so you can identify switched and permanent live separately. Route the cable through the ceiling void and into the fan terminal block, clipping it at 250 mm intervals.

If the fan is being wired to its own pull-cord isolator, take the feed into the isolator first, then run two-core cable on to the fan.

7. Make the connections

Strip conductors carefully. Inside the fan's terminal block, connect: permanent live (brown) to L, switched live (grey or black, sleeved brown at both ends) to the switched-live terminal, neutral (blue) to N, and earth to E. Sleeving the grey or black conductor with brown PVC sleeve at each end identifies it correctly as a switched live, as required by BS 7671.

Do not over-strip the conductors. 8 mm to 10 mm of bare copper is enough for most terminal blocks. Overtighten and you risk crushing the conductors; undertighten and a loose connection will arc under load.

8. Set the over-run timer and test

Most fans have a small recessed adjustment dial or DIP switch accessible once the grille is removed. Set the over-run to two to five minutes for an average bathroom. A longer over-run costs very little in electricity and is more effective at clearing moisture.

Restore power at the consumer unit. Switch the bathroom light on and confirm the fan starts. Switch the light off and time the over-run. Refit the grille. If the fan hums but the impeller does not spin, the capacitor may be faulty or the fan body is obstructed. Do not leave it running in that state.

Stop and call an electrician if: the fan position falls in zone 1 or 2 and you are not certain the fitting carries the correct IP rating; if the existing wiring is rubber-sheathed or there is no earth conductor; if fitting the fan means adding a new cable from the consumer unit rather than tapping an existing circuit; if the MCB or RCD trips when you restore power; or if the ducting route requires penetrating a structural wall and you are not sure what is inside it.

When to call us

A straightforward like-for-like fan replacement on an existing wired position takes Richard about an hour. If there is no existing fan and the wiring needs running from scratch, or the duct route is difficult, book a proper call-out. Damp-related damage in bathrooms costs far more to fix than getting the fan right in the first place.

Need a bathroom fan fitted in Sandwich?

Richard wires and fits bathroom extractor fans with correct zone compliance, over-run timers set, and the duct properly run to the outside.

Contact Richard

Related pages